§ 29-60. Feeder conductors.  


Latest version.
  • The underground feeder conductors shall be copper with Type (R.R.-U.S.E.R.W., or R.H.W., insulation and shall be of sufficient size so that the voltage drop to the last light standard will not exceed five (5) percent. The conductor size in any case shall not be smaller than #8 B & S gauge.

(Code 1961, § 15-23)